Honeywell Searchpoint Optima Plus 2108B2003N – Legacy, Ethylene, ATEX / IECEx, 4–20 mA

2108B2003N is a legacy Honeywell Searchpoint Optima Plus point IR detector (Ethylene), ATEX / IECEx, 4–20 mA, 316SS. New projects should order a current 2108N SKU; keep this page for installed-base replacements.

Siblings: HART —, gas —, style —, approval —.

2108B2003N Honeywell Searchpoint Optima Plus Ethylene Legacy

Part-number decode

SegmentMeaningThis SKU
FamilyHoneywell Searchpoint Optima Plus point IROptima Plus
P/NOptima Plus Point IR Gas Detector,Ethylene,4-20mA,ATEX/IECEx (legacy P/N),316SS2108B2003N
ClassTransmitter LegacyLegacy

Technical specifications

CategoryTransmitter Legacy / Legacy
DescriptionOptima Plus Point IR Gas Detector,Ethylene,4-20mA,ATEX/IECEx (legacy P/N),316SS
GasEthylene
Output4–20 mA
ApprovalsATEX / IECEx
EntriesM25
Enclosure316 不锈钢
RGCno
PrinciplePoint IR (dual source, dual beam)
Range0–100 %LEL (gas curve)
IngressIP66/IP67(探测器)

Why this part number

Legacy 2108B2003N shares the Optima Plus optics with the 2108N range, but approval kits and accessory packs changed. Do not write 2108B2003N into a new PID; read the nameplate before swapping the whole head versus a window/lamp kit.

Spares and mates

2108B2003N is Searchpoint Optima Plus Legacy. The detector is 316SS point IR with the factory window or flow-housing kit. Matrix: product-2698. Do not substitute Sensepoint XCD cartridges or XNX personalities.

Typical applications

2108B2003N shows up on offshore, FPSO pump-room and refinery compressor spare lists. Hydrocarbon SKUs are not ethylene curves.

Selection contrast

P/NTypeGasCertOutput
2108B2003HLegacyEthyleneATEXHART+4–20 mA
2108B2103NLegacyEthyleneUL4–20 mA
2108B2103HLegacyEthyleneULHART+4–20 mA
2108B2043NLegacyEthyleneCU-TR4–20 mA
2108B2043HLegacyEthyleneCU-TRHART+4–20 mA
2108B2053NLegacyEthyleneMED4–20 mA
2108B2053HLegacyEthyleneMEDHART+4–20 mA

Optima Plus family matrix

Installation and service

Mount 2108B2003N on a rigid 316 stand sized for the nameplate mass. Entries are M25 — do not retap. Land 4–20 mA on the fire-and-gas matrix; HART does not replace the trip pair. Keep the weather/deluge kit oriented so water cannot pond on the window. Gas with the Ethylene curve only.

FAQ

Is 2108B2003N a catalytic LEL detector?
No. 2108B2003N is Searchpoint Optima Plus point IR. Catalytic beads are Sensepoint XCD or XNX+MPD.
Can I recertify 2108B2003N from hydrocarbon to ethylene in the field?
No. This SKU is the Ethylene curve. Order sibling — instead of swapping filters.
Does 2108B2003N include HART?
4–20 mA only; HART sibling is —. HART does not replace the trip pair.
Can I convert Standard to Sampling on the lid?
The window kits differ. 2108B2003N is Legacy; the other style is —. Prefer a sampling SKU or flow-housing retrofit kit.
Is 2108B2003N an XNX transmitter?
No. 2108B2003N is the Optima detector head. Pairing with XNX needs a separate IR-personality transmitter.
Can I retap the entries?
No. 2108B2003N is ATEX / IECEx / M25. Other approvals are sibling —.

Documents

Optima Plus datasheet 1 · Datasheet 2 · On-site part-number matrix

Availability and enquiry

Stock is lot-based. If 2108B2003N is out, jump to — / —.

WhatsAppTop