Honeywell Searchpoint Optima Plus 2108B2201H – Legacy, Hydrocarbon, FM / CSA, HART+4–20 mA

2108B2201H is a legacy Honeywell Searchpoint Optima Plus point IR detector (Hydrocarbon), FM / CSA, HART+4–20 mA, 316SS. New projects should order a current 2108N SKU; keep this page for installed-base replacements.

Siblings: HART —, gas —, style —, approval —.

2108B2201H Honeywell Searchpoint Optima Plus Hydrocarbon Legacy

Part-number decode

SegmentMeaningThis SKU
FamilyHoneywell Searchpoint Optima Plus point IROptima Plus
P/NOptima Plus Point IR Gas Detector,Hydrocarbon,HART+4-20mA,FM/CSA (legacy P/N),316SS2108B2201H
ClassTransmitter LegacyLegacy

Technical specifications

CategoryTransmitter Legacy / Legacy
DescriptionOptima Plus Point IR Gas Detector,Hydrocarbon,HART+4-20mA,FM/CSA (legacy P/N),316SS
GasHydrocarbon
OutputHART+4–20 mA
ApprovalsFM / CSA
Entries3/4" NPT
Enclosure316 不锈钢
RGCno
PrinciplePoint IR (dual source, dual beam)
Range0–100 %LEL (gas curve)
IngressIP66/IP67(探测器)

Why this part number

Legacy 2108B2201H shares the Optima Plus optics with the 2108N range, but approval kits and accessory packs changed. Do not write 2108B2201H into a new PID; read the nameplate before swapping the whole head versus a window/lamp kit.

Spares and mates

2108B2201H is Searchpoint Optima Plus Legacy. The detector is 316SS point IR with the factory window or flow-housing kit. Matrix: product-2698. Do not substitute Sensepoint XCD cartridges or XNX personalities.

Typical applications

2108B2201H shows up on offshore, FPSO pump-room and refinery compressor spare lists. Hydrocarbon SKUs are not ethylene curves.

Selection contrast

P/NTypeGasCertOutput
2108B2001NLegacyHydrocarbonATEX4–20 mA
2108B2001HLegacyHydrocarbonATEXHART+4–20 mA
2108B2101NLegacyHydrocarbonUL4–20 mA
2108B2101HLegacyHydrocarbonULHART+4–20 mA
2108B2201NLegacyHydrocarbonFM4–20 mA
2108B2041NLegacyHydrocarbonCU-TR4–20 mA
2108B2041HLegacyHydrocarbonCU-TRHART+4–20 mA

Optima Plus family matrix

Installation and service

Mount 2108B2201H on a rigid 316 stand sized for the nameplate mass. Entries are 3/4" NPT — do not retap. Land 4–20 mA on the fire-and-gas matrix; HART does not replace the trip pair. Keep the weather/deluge kit oriented so water cannot pond on the window. Gas with the Hydrocarbon curve only.

FAQ

Is 2108B2201H a catalytic LEL detector?
No. 2108B2201H is Searchpoint Optima Plus point IR. Catalytic beads are Sensepoint XCD or XNX+MPD.
Can I recertify 2108B2201H from hydrocarbon to ethylene in the field?
No. This SKU is the Hydrocarbon curve. Order sibling — instead of swapping filters.
Does 2108B2201H include HART?
Yes, HART+4–20 mA. HART does not replace the trip pair.
Can I convert Standard to Sampling on the lid?
The window kits differ. 2108B2201H is Legacy; the other style is —. Prefer a sampling SKU or flow-housing retrofit kit.
Is 2108B2201H an XNX transmitter?
No. 2108B2201H is the Optima detector head. Pairing with XNX needs a separate IR-personality transmitter.
Can I retap the entries?
No. 2108B2201H is FM / CSA / 3/4" NPT. Other approvals are sibling —.

Documents

Optima Plus datasheet 1 · Datasheet 2 · On-site part-number matrix

Availability and enquiry

Stock is lot-based. If 2108B2201H is out, jump to — / —.

WhatsAppTop