Honeywell Searchpoint Optima Plus 2108N5410H – Sampling, Hydrocarbon, ATEX / IECEx / MED, HART+4–20 mA

2108N5410H is a Honeywell Searchpoint Optima Plus sampling point IR (Hydrocarbon), ATEX / IECEx / MED, M25, 316SS, HART+4–20 mA, black-anodised flow housing with remote gassing cell (RGC). Order it when the sample is extracted to the head instead of diffusing through a weather cap.

Siblings: HART 2108N5410N, gas —, style 2108N4410H, approval 2108N5010H.

2108N5410H Honeywell Searchpoint Optima Plus Hydrocarbon Sampling

Part-number decode

SegmentMeaningThis SKU
FamilyHoneywell Searchpoint Optima Plus point IROptima Plus
2108NCurrent detector prefix (legacy is 2108B)2108N
4 / 54=Standard diffusion; 5=Sampling5
Approval0=ATEX M25; 1=UL NPT; 2=FM NPT; 4=MED; 6=CCCF4
RGC0=no remote gassing cell; 1=RGC fitted1
Gas0=Hydrocarbon; 1=Ethylene0
OutputN=4–20 mA; H=HART+4–20 mAH

Technical specifications

CategoryTransmitter / Sampling
DescriptionOptima Plus Point IR Gas Detector,Hydrocarbon,HART+4-20mA,ATEX/IECEx/MED,M25,316SS,sampling version with flow housing+RGC
GasHydrocarbon
OutputHART+4–20 mA
ApprovalsATEX / IECEx / MED
EntriesM25
Enclosure316 不锈钢
RGCyes
PrinciplePoint IR (dual source, dual beam)
Range0–100 %LEL (gas curve)
IngressIP66/IP67(探测器)

Why this part number

Sampling SKU 2108N5410H uses a flow housing, not the dust-barrier + weather housing + deluge shade pack. Pressurised pump rooms and cold-box bypasses take this number; open-deck diffusion points take the Standard sibling.

Spares and mates

2108N5410H is Searchpoint Optima Plus Sampling. The detector is 316SS point IR with the factory window or flow-housing kit. Matrix: product-2698. Do not substitute Sensepoint XCD cartridges or XNX personalities.

Typical applications

Park 2108N5410H on LNG boil-off sample taps, solvent-coater ovens and compressor seal-gas extracts. 4–20 mA goes to the fire-and-gas panel; HART is asset management.

Selection contrast

P/NTypeGasCertOutput
2108N5410NSamplingHydrocarbonMED4–20 mA
2108N5400HSamplingHydrocarbonMEDHART+4–20 mA
2108N4410HStandardHydrocarbonMEDHART+4–20 mA
2108N5010HSamplingHydrocarbonATEXHART+4–20 mA
2108N4000NStandardHydrocarbonATEX4–20 mA
2108N4000HStandardHydrocarbonATEXHART+4–20 mA
2108N4010NStandardHydrocarbonATEX4–20 mA

Optima Plus family matrix

Installation and service

Mount 2108N5410H on a rigid 316 stand sized for the nameplate mass. Entries are M25 — do not retap. Land 4–20 mA on the fire-and-gas matrix; HART does not replace the trip pair. Pipe the flow housing into the sample line. Gas with the Hydrocarbon curve only.

FAQ

Is 2108N5410H a catalytic LEL detector?
No. 2108N5410H is Searchpoint Optima Plus point IR. Catalytic beads are Sensepoint XCD or XNX+MPD.
Can I recertify 2108N5410H from hydrocarbon to ethylene in the field?
No. This SKU is the Hydrocarbon curve. Order sibling — instead of swapping filters.
Does 2108N5410H include HART?
Yes, HART+4–20 mA. HART does not replace the trip pair.
Can I convert Standard to Sampling on the lid?
The window kits differ. 2108N5410H is Sampling; the other style is 2108N4410H. Prefer a sampling SKU or flow-housing retrofit kit.
Is 2108N5410H an XNX transmitter?
No. 2108N5410H is the Optima detector head. Pairing with XNX needs a separate IR-personality transmitter.
Can I retap the entries?
No. 2108N5410H is ATEX / IECEx / MED / M25. Other approvals are sibling 2108N5010H.