Honeywell Searchpoint Optima Plus 2108N4001N – Standard, Ethylene, ATEX / IECEx, 4–20 mA

2108N4001N is a Honeywell Searchpoint Optima Plus point IR flammable detector (Ethylene calibration), ATEX / IECEx, M25, 316SS, 4–20 mA, with dust barrier + weather housing + deluge shade without RGC. Use this infrared point where catalytic beads poison or the stream is oxygen-free—do not substitute a Sensepoint XCD pellistor.

Siblings: HART 2108N4001H, gas 2108N4000N, style 2108N5001N, approval 2108N4101N.

2108N4001N Honeywell Searchpoint Optima Plus Ethylene Standard

Part-number decode

SegmentMeaningThis SKU
FamilyHoneywell Searchpoint Optima Plus point IROptima Plus
2108NCurrent detector prefix (legacy is 2108B)2108N
4 / 54=Standard diffusion; 5=Sampling4
Approval0=ATEX M25; 1=UL NPT; 2=FM NPT; 4=MED; 6=CCCF0
RGC0=no remote gassing cell; 1=RGC fitted0
Gas0=Hydrocarbon; 1=Ethylene1
OutputN=4–20 mA; H=HART+4–20 mAN

Technical specifications

CategoryTransmitter / Standard
DescriptionOptima Plus Point IR Gas Detector,Ethylene,4-20mA,ATEX/IECEx,M25,316SS,with dust barrier+weather housing+deluge shade
GasEthylene
Output4–20 mA
ApprovalsATEX / IECEx
EntriesM25
Enclosure316 不锈钢
RGCno
PrinciplePoint IR (dual source, dual beam)
Range0–100 %LEL (gas curve)
IngressIP66/IP67(探测器)

Why this part number

Optima Plus dual-source dual-beam IR does not need oxygen and ignores silicones. 2108N4001N freezes approval, thread, gas curve and output. Ethylene calibration is not interchangeable; RGC lets you gas the cell without a cup, otherwise order the calibration adaptor.

Spares and mates

2108N4001N is Searchpoint Optima Plus Standard. The detector is 316SS point IR with the factory window or flow-housing kit. Matrix: product-2698. Do not substitute Sensepoint XCD cartridges or XNX personalities.

Typical applications

2108N4001N sits on offshore platforms, FPSO cargo pump rooms, refinery compressor halls and solvent print lines. Light hydrocarbons high, heavy vapours at the pit lip, optics out of wash-down.

Selection contrast

P/NTypeGasCertOutput
2108N4001HStandardEthyleneATEXHART+4–20 mA
2108N4000NStandardHydrocarbonATEX4–20 mA
2108N4011NStandardEthyleneATEX4–20 mA
2108N5001NSamplingEthyleneATEX4–20 mA
2108N4101NStandardEthyleneUL4–20 mA
2108N4011HStandardEthyleneATEXHART+4–20 mA
2108N5001HSamplingEthyleneATEXHART+4–20 mA

Optima Plus family matrix

Installation and service

Mount 2108N4001N on a rigid 316 stand sized for the nameplate mass. Entries are M25 — do not retap. Land 4–20 mA on the fire-and-gas matrix; HART does not replace the trip pair. Keep the weather/deluge kit oriented so water cannot pond on the window. Gas with the Ethylene curve only.

FAQ

Is 2108N4001N a catalytic LEL detector?
No. 2108N4001N is Searchpoint Optima Plus point IR. Catalytic beads are Sensepoint XCD or XNX+MPD.
Can I recertify 2108N4001N from hydrocarbon to ethylene in the field?
No. This SKU is the Ethylene curve. Order sibling 2108N4000N instead of swapping filters.
Does 2108N4001N include HART?
4–20 mA only; HART sibling is 2108N4001H. HART does not replace the trip pair.
Can I convert Standard to Sampling on the lid?
The window kits differ. 2108N4001N is Standard; the other style is 2108N5001N. Prefer a sampling SKU or flow-housing retrofit kit.
Is 2108N4001N an XNX transmitter?
No. 2108N4001N is the Optima detector head. Pairing with XNX needs a separate IR-personality transmitter.
Can I retap the entries?
No. 2108N4001N is ATEX / IECEx / M25. Other approvals are sibling 2108N4101N.

Documents

Optima Plus datasheet 1 · Datasheet 2 · On-site part-number matrix

Availability and enquiry

Stock is lot-based. If 2108N4001N is out, jump to 2108N4001H / 2108N5001N.