Honeywell Sensepoint XCD SPXCDALMCX – Fixed CO Detector (0-300ppm, Electrochemical (Surecell™), ATEX, LM25, M20)

SPXCDALMCX is the Sensepoint XCD carbon monoxide variant, 0–300 ppm electrochemical default, LM25 epoxy-coated aluminium, 2 × M20, ATEX / IECEx / GB. Use it on boiler rooms, enclosed car parks and furnace galleries where CO is near-neutral buoyancy and a wall-mounted 4–20 mA point is safer than a clip-on badge.

Same gas, swap enclosure/approval: aluminium SPXCDALMCX, 316SS SPXCDASMCX, UL SPXCDULNCX. SPXCDALMCX · SPXCDASMCX · SPXCDULNCX

SPXCDALMCX Honeywell Sensepoint XCD CO detector LM25 M20

Part-number decode

SegmentMeaningThis SKU
SPXCDSensepoint XCD seriesSPXCD
A / UApproval A=ATEX/IECEx/GB; U=ULA
L / SEnclosure L=LM25 aluminium; S=316SSL
M / NEntry M=M20; N=3/4" NPTM
CXGas carbon monoxide, Electrochemical (Surecell™)CX

Same gas, swap enclosure/approval: aluminium SPXCDALMCX, 316SS SPXCDASMCX, UL SPXCDULNCX.

Technical specifications

Target gasCO / carbon monoxide
PrincipleElectrochemical (Surecell™)
Default range0-300ppm
User FSD window100-1000ppm
Resolution100ppm
Output4–20 mA sink/source + optional Modbus RTU
Supply16–32 VDC (24 VDC nominal)
Power3.7 W
EnclosureLM25 epoxy-coated aluminium
Entries2 × M20
DisplayTri-colour backlight LCD
Relays3×5A@250VAC
IngressIP66
ApprovalsATEX / IECEx / GB
Temperature−40~+65 ℃
Massapprox. 2.0 kg (4.4 lb)

Why this principle for this gas

CO mixes through the occupied layer instead of pooling on the floor. Electrochemical Surecell™ is chosen for ppm resolution and cross-interference control versus catalytic beads that only see flammability. Mount at breathing height (1.5–1.8 m) on the downwind wall of the boiler or parking deck; a floor mount will under-read a stratified plume.

Sensor and replaceable parts

OEM cartridge SPXCDXSCXSS. Calibration cap S3KCAL. Collecting cone follows buoyancy—see installation. Pipe/duct kits: SPXCDMTBR / SPXCDDMK.

Typical applications

Specify this SKU for boiler houses, tunnel plant rooms, sinter galleries and enclosed loading docks. A fixed XCD point gives a hard-wired trip to the ventilation starter and a local tri-colour display; a portable only records the minute you walked past.

Selection contrast

P/NGasRangePrinciple
SPXCDALMCXCO0-300ppmEChem
SPXCDALMHXH₂S0-50ppmEChem
SPXCDALMO1O₂0-25.0%VolEChem
SPXCDALMG1H₂0-1000ppmEChem
SPXCDASMCXCO0-300ppmEChem
SPXCDULNCXCO0-300ppmEChem

XCD family matrix

Installation and wiring

Wall-mount SPXCDALMCX (carbon monoxide, LM25 epoxy-coated aluminium) through the one-piece plate with M8 bolts sized for that mass. This SKU uses 2 × M20 entries: pipe kit SPXCDMTBR covers Ø1.5–3″, duct kit is SPXCDDMK, and glands must match—do not retap SPXCDALMCX. Land SPXCDALMCX 4–20 mA as three-wire and set Modbus address from the menu only. Magnetic wand calibration on the SPXCDALMCX lid stays non-intrusive. On SPXCDALMCX hold CO at breathing height on the downwind wall.

FAQ

SPXCDALMCX: Is the 0–300 ppm CO range field-adjustable?
SPXCDALMCX — Yes, the user FSD window is 100–1000 ppm in 100 ppm steps. Leave 300 ppm for occupied rooms; lift FSD only if a process vent can exceed that.
SPXCDALMCX: Will hydrogen interfere with the CO cell?
SPXCDALMCX — Short H₂ transients can read as CO. If the room also handles hydrogen, add a dedicated G1 point rather than relying on this CX cell alone.
LM25 or 316SS for SPXCDALMCX (carbon monoxide)?
SPXCDALMCX ships in LM25 epoxy aluminium (~4.4 lb). For carbon monoxide in salt spray, caustic CIP or sour-water splash, switch to 316SS sibling SPXCDASMCX instead of painting this lid.
Can I convert SPXCDALMCX from ATEX M20 to NPT in the field?
No. SPXCDALMCX flameproof entries are machined M20. North-American NPT is UL sibling SPXCDULNCX, not an adaptor on this ATEX carbon monoxide body.
Can I retrofit Modbus on SPXCDALMCX after it ships?
Modbus RTU on SPXCDALMCX is a transmitter sales option, not a jumper on the carbon monoxide lid. Confirm the option before the box leaves; 4–20 mA sink/source is already on this SKU.

Documents

Honeywell Sensepoint XCD datasheet / manual · On-site XCD selection matrix

Availability and enquiry

Stock is lot-based. If this aluminium ATEX box is out, jump to 316SS SPXCDASMCX or UL SPXCDULNCX rather than a dead SKU.